electricpy.fault.tdradial¶
- electricpy.fault.tdradial(I, CTI, Ipu_up, Ipu_dn=0, TDdn=0, curve='U1', scale=2, freq=60, CTR_up=1, CTR_dn=1, tfixed=None)[source]¶
Radial Time Dial Coordination Function.
Function to evaluate the Time-Dial (TD) setting in radial schemes where the Coordinating Time Interval (CTI) and the up/downstream pickup settings are known along with the TD setting for the downstream protection.
- Parameters:
I (float) – Measured fault current in Amps, typically set using the maximum fault current available.
CTI (float) – Coordinating Time Interval in cycles.
Ipu_up (float) – Pickup setting for upstream protection, specified in amps
Ipu_dn (float, optional) – Pickup setting for downstream protection, specified in amps, default=0
TDdn (float, optional) – Time-Dial setting for downstream protection, specified in seconds, default=0
curve (string, optional) – Name of specified TOC curve, may be entry from set: {U1,U2,U3,U4,U5,C1,C2,C3,C4,C5}, default=U1
scale (int, optional) – Scaling value used to evaluate a practical TD setting, default=2
freq (float, optional) – System operating frequency, default=60
CTR_up (float, optional) – Current Transformer Ratio for upstream relay. default=1
CTR_dn (float, optional) – Current Transformer Ratio for downstream relay. default=1
tfixed (float, optional) – Used to specify a fixed time delay for coordinated protection elements, primarily used for coordinating TOC elements (51) with OC elements (50) with a fixed tripping time. Overrides downstream TOC arguments including Ipu_dn and TDdn.
- Returns:
TD – Calculated Time-Dial setting according to radial scheme logical analysis.
- Return type:
float