electricpy.fault.single_phase_to_ground_fault¶
- electricpy.fault.single_phase_to_ground_fault(Vth, Zseq, Rf=0, sequence=True, reference='A')[source]¶
Single-Phase-to-Ground Fault Calculator.
This function will evaluate the Zero, Positive, and Negative sequence currents for a single-line-to-ground fault.
\[I_1 = \frac{V_{th}}{Z_0+Z_1+Z_2+3*R_f}\]\[I_2 = I_1\]\[I_0 = I_1\]- Parameters:
Vth (complex) – The Thevenin-Equivalent-Voltage
Zseq (list of complex) – Tupple of sequence reactances as (Z0, Z1, Z2)
Rf (complex, optional) – The fault resistance, default=0
sequence (bool, optional) – Control argument to force return into symmetrical- or phase-domain values.
reference ({'A', 'B', 'C'}) – Single character denoting the reference, default=’A’
- Returns:
Ifault – The Array of Fault Currents as (If0, If1, If2)
- Return type:
list of complex,