electricpy.fault.highzmini¶
- electricpy.fault.highzmini(N, Ie, Irly=None, Vset=None, Rrly=2000, Imov=0, CTR=1)[source]¶
Minimum Current for High Impedance Protection Calculator.
Evaluates the minimum pickup current required to cause high-impedance bus protection element pickup.
- Parameters:
N (int) – Number of Current Transformers included in scheme
Ie (float) – The excitation current at the voltage setting
Irly (float, optional) – The relay current at voltage setting
Vset (float, optional) – The relay’s voltage pickup setting in volts.
Rrly (float, optional) – The relay’s internal resistance in ohms, default=2000
Imov (float, optional) – The overvoltage protection current at the voltage setting. default=0.0
CTR (float, optional) – Current Transformer Ratio, default=1
- Returns:
Imin – Minimum current required to cause high-impedance bus protection element pickup.
- Return type:
float